11
DDC Controller for Tempered Air Products
Menu Overview
Press
Prg
to enter menus.
c. BMS Config
d. Service Settings
Service
Manufacturer
Service Password
Insert service
password (PW1): 0000
Service Password
Insert service
password (PW1): 0000
Manufacturer Password
Insert service
password (PW1): 0000
BACnet Read/Write
Function: Read
Update? Yes
*Cycle unit power to
confirm write command.
a. Working hour set
a. Configuration
c. Factory settings
c. Password/Defaults
b. Probe adjustment
Probe Adjust
pCOe number: 1
Offset Ch 1: 0.0
Offset Ch 2: 0.0
Offset Ch 3: 0.0
Offset Ch 4: 0.0
Digital Compressor
Minimum OFF: 1.0vdc
Minimum ON: 1.9vdc
Maximum: 5.0vdc
Delay OFF: 60s
Max Power Start: 120s
Hot Gas Controller
Integration: 300s
Band: 20°F
Unoccupied Mode Setup
Type: CycleSupplyFan
Source: Input ID6
TCP/IP SETUP
Instance: 77000
IP set by: DHCP
IP: 172.016.000.001
Subnet: 255.255.255.000
Gatewy: 192.168.001.001
Analog Input
Cold Coil Temperature
Input B03:
###.#°F
Offset: 0.0°F
Value: ###.#°F
Analog Output Config
Wheel
Channel: Y1
Action: DIRECT
Minimum: #.#vdc
Maximum: ##.#vdc
Cooling Controller
Integration: 300s
Band: 20°F
Reheat Setup
Will heater be used
for reheat during
dehumidification?
Reheat: Disable
Supply Reset Control
Integration: 1200s
Band: 10°F
Wheel Rotation Sensor
Alarm delay: 30s
(input ID3)
TCP/IP SETUP
DNS 1: ###.###.###
DNS 2: ###.###.###
Type: IP
Analog Input
Room Temperature
Input B04:
###.#°F
Offset: 0.0°F
Value: ###.#°F
Compressor Setup
# of stages: #
Rotation: LIFO
Reheat Setup 2
Will heater be used
for reheat along
with hot gas?
Heater: Disable
Heat/Cool Delay
Time delay between
heating, cooling &/or
economizer modes.
Delay: 180s
Temperature Scale
Select: Fahrenheit
Display Buzzer
Select: Disable
User Default
Insert new service
password (PW1): 0000
Unit BMS Control
Unit Start/Stop: Yes
Temp Setpoint: Local
Occupancy: Input ID6
BMS Configuration
Protocol: None
BACnet Plugin? Yes
MAINTENANCE HOURS
SYSTEM
Run hours: 0000h
Set Point: 0000h
Reset to Zero? No
Unit Code
Select DDC configur-
ation code here.
Code: GWXXXXXXX00
Analog Input
Outside Temperature
Channel:B1
Type: NTC
Offset: #.#°F
Value: ##.#°F
Factory Setup
Consult Factory
Before Altering
Compressor Timers
Minimum ON: ###s
Minimum OFF: ###s
Between Stages: ###s
Hot Gas Setup
Hot gas reheat coil
minimum on/off
time: 10minutes
Damper Setup
Allow the dampers to
open for: 10 seconds
before starting the
fans.
Factory Settings
Save? No
Restore? No
User Default settings
Save? No
Restore? No
BMS Write Points
TempSetpoint: aaa.a°F
Start/Stop: Stop
Reset Alarms: No
Occupancy: Occ
MODBUS SETUP
Address: 1
Baudrate 9600
Analog Input
Outside Temperature
Input B01:
###.#°F
Offset: 0.0°F
Value: ###.#°F
Unit Expansion Comm
Field Card Settings
Baudrate: 19200
Stop bit: 2
Parity mode: NONE
Timeout: 300ms
Digital Input
Supply Fan
Channel: ID1
Action: OPEN
Delay: 0s
Open
Economizer Controller
Integration 300s
Band: 20°F
Econo ON/OFF times:
Minimum ON: 300s
Minimum OFF: 300s
Compressor Staging
Stage1: ON @ 50% OFF 0%
Stage2: ON @ 100% OFF 50%
Fan/Airflow Proving
Alarm delay: 30s
(inputs ID1 & ID5)
Hot Gas Flush Setup
Cycle: 30minutes
Duration: 1minutes
New Password
Insert new manufacturer
password (PW2): ####
MSTP SETUP
Instance: 77000
Baudrate 38400
MAC Addr: 0
MaxMasters: 127
MaxInfoFrames: 10
Analog Input
Discharge Temperature
Input B02:
###.#°F
Offset: 0.0°F
Value: ###.#°F
Unit Expansion I/O
Enable Expansion: No
Relay Output
Defrost
Channel: 1
Status: OFF
Supply Fan Cycling
Defrost setup
Fan off time: 5min
Fan on time: 30min
Heater Controller
Integration: 300s
Band: 20°F
Mod Hot Gas Setup
Minimum On: 4.0vdc
Maximum On: 10.0vdc
Fan Delay
Time delay between
starting of supply
& exhaust fans.
Fan delay: 15s
Initialization
DEFAULT INSTALLATION
Erase user settings
and install global
default values: No
b. I/O Configuration
All I/O points are included An example of each is shown.
d. Initialization
®